Type | DC24V, Nomal Type, Restorable Type, Air Sampling Type, Analog Type, Range of nominal detection concentraion,(1%/m~10%/m), One inlet pipes, Maximum pipe lengh depending on number of inlets : 70m, model :ASD 532 |
---|---|
Type approval No | 감24-27 |
Ambient temperature | -20~60ºC |
Ambient Voltage | 14.0-30 VDC (EN54) 16.4~27 VDC(FM/UL) |
Low-noise | 24.5~39dBA |
Dimensions | 195 X 140 X 290(mm) (W x D x H) |
Weight | 1950g |
Air distribution pressure | 180Pa |
Sensitivity range | 1%/m~10%/m |
Relative humidity | 10~85% |
Max air pipe connection length | 70m |
Protection rating | IP54 |
Material | ABS b lend, UL 94-V 0 |
Simulation programing | PipeFlow |
Fire safety standard | NFSC203 Article 7 |